|
|
Electronics, Instrumentation & Electrical Database
Sensors and Transducers Suppiers Menu
Testing industrial equipment electrical wiring insulation may be a critical maintenance event to predict and correct electrical insulation failure.
The failure of an insulation system is the most
common cause of problems in electrical equipment.
Insulation is subject to many effects which can
cause it to fail; such as mechanical damage, vibration,
excessive heat or cold, dirt, oil, corrosive vapors,
moisture from processes, or just the humidity
on a muggy day. As pin holes or cracks develop,
moisture and foreign matter penetrate the surfaces
of the insulation, providing a low resistance path for
leakage current. Sometimes the drop in insulation resistance is sudden, as when equipment is flooded. Usually, however, it drops gradually, giving plenty
if warning, if checked periodically. Such checks permit planned reconditioning before service failure. Before testing the insulation on active industrial equipment, adhere to the following:
Take the equipment to be tested out of service.
This involves de-energizing the equipment and
disconnecting it from other equipment and circuits. If disconnecting the equipment from the circuit
cannot be accomplished, then inspect the installation
to determine what equipment is connected
and will be included in the test. Pay
particular attention to conductors that lead away
from the installation. This is very important because
the more equipment that is included in a test,
the lower the reading will be, and the true insulation
resistance of the apparatus in question may be
masked by that of the associated equipment. It is
always possible, of course, that the insulation resistance
of the complete installation will be satisfactory,
especially for a spot check. Or, it may be higher
than the range of the ohmmeter, in which case
nothing would be gained by separating the components
because the insulation resistance of each part
would be still higher.
Test for foreign or induced voltages with a
volt-ohm-milliammeter. Pay particular attention
once again to conductors that lead away from the
circuit being tested and make sure they have been
properly disconnected from any source of voltage.
Large electrical equipment and cables usually
have sufficient capacitance to store a dangerous
amount of energy from the test current. Therefore,
discharge capacitance both before and after any
testing by short circuiting and grounding the equipment
and cables under test. Consult manufacturer’s
bulletins and pertinent references to determine,
prior to such shorting or grounding, if a specified
“discharge” or “bleed” or “grounding” resistor should
be used in the shorting/grounding circuit to limit
the magnitude of the discharge current.
Generally, there is no fire hazard in the
normal use of a ohmmeter. There is, however, a
hazard when testing equipment located in inflammable
or explosive atmospheres. Slight sparking
may be encountered when attaching test leads to
equipment in which the capacitance has not been
completely discharged or when discharging capacitance
following a test. It is therefore suggested that
use of a ohmmeter in an explosive atmosphere be avoided if at all possible. If however testing must
be conducted in an explosive atmosphere, then it is
suggested that test leads not be disconnected for at
least 30 to 60 seconds following a test, so as to allow
time for capacitance discharge.
Do not use a ohmmeter whose terminal
operating voltage exceeds that which is safe to apply
to the equipment under test.
To take a spot insulation reading, connect the
ohmmeter across the insulation to be tested and
operate it for a short, specific timed period (60 seconds
usually is recommended). Bear in mind also
that temperature and humidity, as well as the condition
of your insulation, affect your reading. Your
very first spot reading on equipment, with no prior
test, can be only a rough guide as to how “good” or
“bad” the insulation is. By taking readings periodically
and recording them, you have a better basis of
judging the actual insulation condition. Any persistent
downward trend is usually fair warning of
trouble ahead, even though the readings may be
higher than the suggested minimum safe values.
Equally true, as long as your periodic readings are
consistent, they may be OK, even though lower than
the recommended minimum values. You should
make these periodic tests in the same way each
time, with the same test. connections and with the
same test voltage applied for the same length of
time.
Another eletrical wire insulation test method is the time resistance
method. It is fairly independent of temperature
and often can give you conclusive information
without records of past tests. You simply take
successive readings at specific times and note the
differences in readings. Tests by this method are
sometimes referred to as absorption tests. Test voltages
applied are the same as those for the spot
reading test. Note that good insulation shows a continual
increase in resistance over a period of time. If
the insulation contains much moisture or contaminants’
the absorption effect is masked by a high
leakage current which stays at a fairly constant
value-keeping the resistance reading low. The
time resistance test is of value also because it is
independent of equipment size.
© Copyright 2000 - 2009, by Engineers Edge, LLC All rights reserved.
Disclaimer
|